NIST Technical Note 1603

Experimental Study of the Effects of Fuel Type, Fuel Distributions, and Vent Size on Full-Scale Underventilated Compartment Fires in an ISO 9705 Room

This is an explanation of the variable names used in the data files.  A text version of this list can be found here.

Variable Name

Explanation

Time

Time from the ignition of the fire

O2Front

Dry Oxygen volume fraction at front sample location

CO2Front

Dry Carbon Dioxide volume fraction at front sample location

COFront

Dry Carbon Monoxide volume fraction at front sample location

UHFront

Dry Unburnt Hydrocarbon volume fraction at front sample location

TFSampPtRh

Temperature in degrees Celsius of bare bead Type R Thermocouple at front sample location

O2Rear

Dry Oxygen volume fraction at rear sample location

CO2Rear

Dry Carbon Dioxide volume fraction at rear sample location

CORear

Dry Carbon Monoxide volume fraction at rear sample location

UHRear

Dry Unburnt Hydrocarbon volume fraction at rear sample

TRSampPtRh

Temperature in degrees Celsius of bare bead Type R Thermocouple at rear sample location

O2Move

Dry Oxygen volume fraction at the movable probe location

CO2Move

Dry Carbon Dioxide volume fraction at the movable probe location

COMove

Dry Carbon Monoxide volume fraction at the movable probe location

UHMove

Dry Unburnt Hydrocarbon volume fraction at the movable probe location

TRMoveSamp

Temperature in degrees Celsius of aspirated Type K thermocouple at movable probe location

Zmove

Vertical location of the movable sample probe

HFRFL

Heat Flux in kW/m^2 at the rear floor location

HFFFL

Heat Flux in kW/m^2 at the front floor location

HFOFL

Heat Flux in kW/m^2 outside the door of the enclosure

HFRCE

Heat Flux in kW/m^2 at the rear ceiling location

HFCCE

Heat Flux in kW/m^2 at the center ceiling location

HFFCE

Heat Flux in kW/m^2 at the front ceiling location

THFRFL

Temperature of the Heat Flux gauge in degrees Celsius at the rear floor location

THFFFL

Temperature of the Heat Flux gauge in degrees Celsius at the front floor location

THFOFL

Temperature of the Heat Flux gauge in degrees Celsius outside the door of the enclosure

THFRCE

Temperature of the Heat Flux gauge in degrees Celsius at the rear ceiling location

THFCCE

Temperature of the Heat Flux gauge in degrees Celsius at the center ceiling location

THFFCE

Temperature of the Heat Flux gauge in degrees Celsius at the front ceiling location

TSHFRFL

Temperature of the enclosure surface near the Heat Flux gauge in degrees Celsius at the rear floor location

TSHFFFL

Temperature of the enclosure surface near the Heat Flux gauge in degrees Celsius at the front floor location

TSHFOFL

Temperature of the enclosure surface near the Heat Flux gauge in degrees Celsius outside the door of the enclosure

TSHFRCE

Temperature of the enclosure surface near the Heat Flux gauge in degrees Celsius at the rear ceiling location

TSHFCCE

Temperature of the enclosure surface near the Heat Flux gauge in degrees Celsius at the center ceiling location

TSHFFCE

Temperature of the enclosure surface near the Heat Flux gauge in degrees Celsius at the front ceiling location

TSXHFRFL

Temperature of the external enclosure surface near the Heat Flux gauge in degrees Celsius at the rear floor location

TSXHFFFL

Temperature of the external enclosure surface near the Heat Flux gauge in degrees Celsius at the front floor location

TSXHFRCE

Temperature of the external enclosure surface near the Heat Flux gauge in degrees Celsius at the rear ceiling location

TSXHFCCE

Temperature of the external enclosure surface near the Heat Flux gauge in degrees Celsius at the center ceiling location

TSXHFFCE

Temperature of the external enclosure surface near the Heat Flux gauge in degrees Celsius at the front ceiling location

Mass1

Mass measurement of pan burner at position 1 (center of room)

Mass2

Mass measurement of pan burner at position 2 (rear center of room)

TR3

Temperature in degrees Celsius of bare bead Type K  thermocouple in rear thermocouple tree at 3 cm above the floor

TR30

Temperature in degrees Celsius of bare bead Type K  thermocouple in rear thermocouple tree at 30 cm above the floor

TR60

Temperature in degrees Celsius of bare bead Type K  thermocouple in rear thermocouple tree at 60 cm above the floor

TR90

Temperature in degrees Celsius of bare bead Type K  thermocouple in rear thermocouple tree at 90 cm above the floor

TR105

Temperature in degrees Celsius of bare bead Type K  thermocouple in rear thermocouple tree at 105 cm above the floor

TR120

Temperature in degrees Celsius of bare bead Type K  thermocouple in rear thermocouple tree at 120 cm above the floor

TR135

Temperature in degrees Celsius of bare bead Type K  thermocouple in rear thermocouple tree at 135 cm above the floor

TR150

Temperature in degrees Celsius of bare bead Type K  thermocouple in rear thermocouple tree at 150 cm above the floor

TR180

Temperature in degrees Celsius of bare bead Type K  thermocouple in rear thermocouple tree at 180 cm above the floor

TR210

Temperature in degrees Celsius of bare bead Type K  thermocouple in rear thermocouple tree at 210 cm above the floor

TR237

Temperature in degrees Celsius of bare bead Type K  thermocouple in rear thermocouple tree at 237 cm above the floor

TF3

Temperature in degrees Celsius of bare bead Type K  thermocouple in front thermocouple tree at 3 cm above the floor

TF30

Temperature in degrees Celsius of bare bead Type K  thermocouple in front thermocouple tree at 30 cm above the floor

TF60

Temperature in degrees Celsius of bare bead Type K  thermocouple in front thermocouple tree at 60 cm above the floor

TF90

Temperature in degrees Celsius of bare bead Type K  thermocouple in front thermocouple tree at 90 cm above the floor

TF105

Temperature in degrees Celsius of bare bead Type K  thermocouple in front thermocouple tree at 105 cm above the floor

TF120

Temperature in degrees Celsius of bare bead Type K  thermocouple in front thermocouple tree at 120 cm above the floor

TF135

Temperature in degrees Celsius of bare bead Type K  thermocouple in front thermocouple tree at 135 cm above the floor

TF150

Temperature in degrees Celsius of bare bead Type K  thermocouple in front thermocouple tree at 150 cm above the floor

TF180

Temperature in degrees Celsius of bare bead Type K  thermocouple in front thermocouple tree at 180 cm above the floor

TF210

Temperature in degrees Celsius of bare bead Type K  thermocouple in front thermocouple tree at 210 cm above the floor

TF237

Temperature in degrees Celsius of bare bead Type K  thermocouple in front thermocouple tree at 237 cm above the floor

CalCO

Dry Carbon Dioxide volume fraction at the calorimetry measurement in the hood

CalCO2

Dry Carbon Monoxide volume fraction at the calorimetry measurement in the hood

CalO2

Dry Oxygen volume fraction at the calorimetry measurement in the hood

IHRR

Complete combustion heat release rate in kW based on the liquid pump flow rate for sprayed liquid fuels gas flow meter for gaseous fuels and mass loss rate for solid fuels and liquid fuels burned in a pan.

HRR2

Measured Heat Release Rate in kW

YsootF

Wet Soot mass fraction at the front sample location

zloc

Location in Z-direction in cm of movable probe at any given time.

 