FASTData January 1999 Release| Descriptions | |
| FDMS: | Obtaining Data |
| Material: | Foam Mattress |
| Lab: |
National Institute of Standards and Technology Building and Fire Research Laboratory |
| Sponsor: |
National Institute of Standards and Technology Building and Fire Research Laboratory |
| Date: | 2/9/1996 |
| Test Ref No: | 1 |
| Tested by: | Henri Mitler |
| Approved by Scientific Officer: | Walter Jones |
| Publication Status: | Unpublished |
| Statistical Basis of Data: | Data available for the same material, but from a different test method |
| Material Development/ Production Status: | Material currently in production |
| Evaluation Status: | Data have been validated |
| Laboratory Accreditation Status: | The laboratory is recognized by (inter)national accreditation bodies |
| Completeness of Material Description: | Partial information on material |
| Completeness of Test Procedure Description: | Ad hoc test, well documented |
Center mattress fire time-line. This test was performed at BFRL in February 1996. Times are in seconds from ignition.
| 0 s, 10 kW | 30 s, 15 kW | 60 s, 50 kW | 90 s, 240 kW |
![]() |
![]() |
![]() |
![]() |
| 120 s, 500 kW | 150 s, 740 kW | 180 s, 650 kW | 210 s, 640 kW |
![]() |
![]() |
![]() |
![]() |
| 240 s, 530 kW | 270 s, 330 kW | 300 s, 180 kW | |
![]() |
![]() |
![]() |
| Mpeg movie of center mattress fire (1.4 MB) | Quicktime movie of center mattress fire (1.4 MB) |
![]() |
![]() |