FASTData January 1999 Release| Descriptions | |
| FDMS: | Obtaining Data |
| Material: | Wood pallet |
| Lab: |
National Institute of Standards and Technology Building and Fire Research Laboratory |
| Sponsor: |
National Institute of Standards and Technology Building and Fire Research Laboratory |
| Date: | 2/9/1996 |
| Test Ref No: | 1 |
| Tested by: | Henri Mitler |
| Approved by Scientific Officer: | Walter Jones |
| Publication Status: | Unpublished |
| Statistical Basis of Data: | Single point value |
| Material Development/ Production Status: | Material currently in production |
| Evaluation Status: | Data have been validated |
| Laboratory Accreditation Status: | The laboratory is recognized by (inter)national accreditation bodies |
| Completeness of Material Description: | Partial information on material |
| Completeness of Test Procedure Description: | Ad hoc test, well documented |
Pallet fire time-line. This test was performed at BFRL in February 1996. Times are in seconds from ignition.
| 0 min, 0 kW | 2 min, 150 kW | 4 min, 390 kW | 6 min, 680 kW |
![]() |
![]() |
![]() |
![]() |
| 8 min, 1.0 MW | 10 min, 1.7 MW | 12 min, 1.6 MW | 14 min, 1.1 MW |
![]() |
![]() |
![]() |
![]() |
| 16 min, 850 kW | 18 min, 560 kW | 20 min, 360 kW | |
![]() |
![]() |
![]() |
| Mpeg movie of Pallet Fire (1.5 Mb) | Quicktime movie of Pallet Fire (1.5 Mb) |
![]() |
![]() |