FASTData January 1999 Release

Test Type: Free burn, Test Number: 1, Description File: BBB1



Descriptions
FDMS: Obtaining Data
Material: Bunk bed
Lab: National Institute of Standards and Technology
Building and Fire Research Laboratory
Sponsor: National Institute of Standards and Technology
Building and Fire Research Laboratory
Date: 2/9/1996
Test Ref No: 1
Tested by: Henri Mitler
Approved by
Scientific Officer:
Walter Jones

Test Quality Indicators

Publication Status:Unpublished
Statistical Basis of Data:Single point value
Material Development/
Production Status:
Material currently in production
Evaluation Status:Data have been validated
Laboratory
Accreditation Status:
The laboratory is recognized by (inter)national accreditation bodies
Completeness of
Material Description:
Partial information on material
Completeness of Test
Procedure Description:
Ad hoc test, well documented

Test Results (summary)

Still Pictures

This test was performed at BFRL in February 1996. Times are in seconds from ignition.
156 s, 10 kW 168 s, 10 kW 180 s, 30 kW 192 s, 120 kW
204 s, 260 kW 216 s, 1.1 MW 228 s, 3.2 MW 240 s, 4.6 MW
252 s, 3.6 MW 264 s, 2.5 MW 276 s, 1.8 MW 288 s, 1.6 MW
300 s, 1.3 MW 312 s, 1.1 MW 324 s, 900 kW 336 s, 820 kW

Movies

View a movie by selecting one of the following images.
Mpeg movie of Bunk Bed Fire (878 Kb) Quicktime movie of Bunk Bed Fire (857 Kb)

Data Plots

Heat Release Rate


FASTData Home
Building and Fire Research Laboratory
National Institute of Standards and Technology
Gaithersburg, MD 20899