BFRL ICON Report of In-Rack Sprinkler Comparison Fire Tests.


pdf icon Report of In-Rack Sprinkler Comparison Fire Tests. (6213 K)
Underwriters Laboratories, Incorporated

NC1838-97NK31099; 36 p. May 22, 1998.

Sponsor:

HSB Industrial Risk Insurers, Hartford, CT

Keywords:

sprinklers; sprinkler systems; fire tests; pallet storage; ignition; oxygen consumption; heat release rate; test facilities; instruments; scenarios

Abstract:

Eight fire tests were conducted to evaluate and compare the level of protection provided by 1/2 in. nominal orifice in-rack sprinklers operating at a flowing pressure of 30 psi and 17/32 in. nominal orifice in-rack sprinklers flowing at 30 gpm. The fire tests were conducted in a double row rack storage array with in-rack sprinklers. Ignition was accomplished with two half cotton cellulose ignitors positioned 18 in. from the aisle. The in-rack sprinklers for Fire Test Nos. 4 and 6 were standard response 1/2 in. nominal orifice 165 deg F temperature rated sprinklers positioned in the longitudinal flue at the center of the bay on one level. The sprinkler was arranged to operate at a flowing pressure of 30 psi. The in-rack sprinkler for Fire Test Nos. 1 and 7 were standard response 1/2 in. nominal orifice 165 deg F temperature rated sprinklers positioned in the longitudinal flue at the rack uprights on one level. The sprinkler was arranged to operate at a flowing pressure of 30 psi. The in-rack sprinklers for Fire Test Nos. 3 and 5 were the standard response 17/32 in. nominal orifice 165 deg F temperature rated sprinklers positioned in the longitudinal flue at the center of the bay on one level. The sprinkler was arranged to operate at a flow of 30 gpm. The in-rack sprinkler for Fire Test Nos. 2 and 8 were the standard response 17/32 in. nominal orifice 165 deg F temperature rated sprinklers positioned in the longitudinal flue at the rack uprights on one level. The sprinklers were arranged to operate at a flow of 30 gpm per sprinkler. The tests were conducted under an oxygen consumption calorimeter to measure the heat release rates. A Table E-1 provides the testing parameters and results obtained. A complete description of the testing is presented in the following report.



Return to BFRL Publications

Building and Fire Research Laboratory
National Institute of Standards and Technology
Gaithersburg, MD 20899